Ampe kìm FLUKE 773 (100mA)

Liên hệ để biết giá

  • Thông số kỹ thuật
  • Thông tin hãng sản xuất
Chi tiết sản phẩm
- mA (kìm kẹp):
+ 0 đến 20.99 mA /0.2% + 2 counts
+ 21.0mA đến 100.0 mA /1% + 5 counts
mA (đo nối tiếp)
+ 0 đến 24.00 mA /0.2% + 2 counts
- mA tạo nguồn (Max 24 mA trong 1,000 ohms)
+ 0 đến 24.00 mA /0.2% + 2 counts
- Tạo mA mô phỏng (Max 50 V dc)
+ 0 đến 24.00 mA /0.2% + 2 counts
- Tạo nguồn điện áp (2 mA max)
+ 0 đến 10.00 V dc /0.2% + 2counts
- Đo điện áp
+ 0 đến 30.00 V dc /0.2% + 2counts
Kích thước vòng kìm: 0.177” or 4.5 mm max
Cấp bảo vệ: IP 40
Kích thước: 59 x 38 x 212 mm, (2.32 x 1.5 x 8.35 in.)
Trọng lượng: 260G, (9.1 oz.)
Phụ kiện: túi mềm, HDSD

Chi tiết
The 773 mA Clamp Meter features:
Best in class 0.2 % accuracy
0.01 mA resolution and sensitivity
Measure 4 to 20 mA signals without ”breaking the loop”
Measure mA signals for PLC and control system analog I/O
Dual backlit display with both mA measurement and percent of 4 to 20 mA span
Measurement Spotlight illuminates hard to see wires in dark enclosures
Detachable clamp with extension cable for measurements in tight locations
Measure 10 to 50 mA signals in older control systems using the 99.9 mA range
Automatically change the 4 to 20 mA output for remote testing
Power saving features, auto-off, backlight timeout extend battery life
Hold function captures and displays changing measurements
Measure 4 to 20 mA signals with in-circuit measurement
Simultaneous mA in-circuit measurement with 24V loop power for powering and testing transmitters
Source 4 to 20 mA signals for testing control system I/O or I/Ps
mA output linear ramp or 25% step output
Automatically change the 4 to 20 mA output for remote testing
DC voltage measurement to verify 24V power supplies or voltage I/O signals
Source DC voltage to test input devices that accept a 1-5V or 0 to 10V signals
Scaled mA output provides a continuous mA signal that corresponds to the 4 to 20 mA signal measured by the mA clamp
Enables milliamp signal logging to a separate logging device without breaking the loop
Output mA signal enables a logging DMM or other device to record the 4- to 20 mA signal without breaking the loop
mA in/out: simultaneously measure the mA signal with the clamp and source a mA signal
Apply a mA input signal to a device and measure its’ 4-20 mA output on devices such as valves or mA isolators
Voltage output linear ramp or 25% step output
Automatically change the voltage output for remote testing
What’s the difference between the 77X models?
.
Fluke-771
Fluke-772
Fluke-773
.
Non-contact mA loop measurement
Integrated mA loop troubleshooting
Advanced process troubleshooting
mA measure, jaw
mA measure, in circuit .
Loop power .
mA source .
DCV measure . .
DCV source . .
mA scaled output . .
mA in / out . .
Environmental Specifications
Diameter of measurable conductor 0.177” or 4.5 mm max
Operating temperature -10 to 50 ºC
Storage Temperature -25 to 60ºC
Operating Humidity < 90% @ <30 c="" 75="" 30="" to="" 55="" c="" td="">
Operating Altitude 0 to 2000 m
IP Rating IP 40
Size 44 x 70 x 246 mm (2 7/8 x 5 ¾ x 11 5/8 in)
Weight 410 g, (14.4 oz)
Vibration Random 2 g, 5 to 500 Hz
Shock 1 meter drop test (except the jaw)
EMI/RFI Meets EN61326-1
Note: For current measurement w/ JAW, add 1mA to
specification for EMC field strengths of 1V/m up to 3V/m.
Temperature Coefficient 0.01% ºC
(<18ºC or > 28ºC)
Power, battery life (4) AA 1.5 V Alkaline, IEC LR6, 12 hours in mA source into 500 ohms
Warranty Three years for electronics
one year for cable and clamp assembly
Functional Specifications
mA measurement
(Measured by clamp) 771/772/773
Resolution and Range: 0 to 20.99 mA
Accuracy: 0.2%+2 counts
Resolution and Range: 21.0 mA to 100.0 mA
Accuracy: 1% + 5 counts
mA measurement
(Measured in series with test jacks) 772/773
Resolution and Range: 0 to 24.00 mA
Accuracy: 0.2% + 2counts
mA source (Maximum mA Drive:
24 mA into 1,000 ohms)
Resolution and Range: 0 to 24.00 mA
Accuracy: 0.2% + 2counts
mA simulate
(Maximum voltage 50 V dc)
Resolution and Range: 0 to 24.00 mA
Accuracy: 0.2% + 2counts
Voltage source (2 mA maximum drive current) Resolution and Range: 0 to 10.00 V dc
Accuracy: 0.2% + 2counts
Voltatge Mesaure Resolution and Range: 0 to 30.00 V dc