Thiết bị đo tỷ số máy biến áp EPHIPOT EPTTR-C (0.9~10000)

Liên hệ để biết giá

  • Thông số kỹ thuật
  • Thông tin hãng sản xuất
Chi tiết sản phẩm
Dải đo: 0.9~10000
Độ chính xác:
±(Gía trị đọc×0.1%+2 digits)(≤500)
±(Gía trị đọc×0.2%+2 digits)(>500≤3000)
±(Gía trị đọc×0.3%+2 digits)(>3000)
Độ phân giải:
0.9~9.9999(0,0001)
10~99.999(0,001)
100~999.99(0,01)
1000~9999.9(0,1)
10000 trở lên(1)
Nguồn điện : AC220V±10%, 50Hz (Option - pin tích hợp)
Trọng lượng : 3.5 kg
Kích thước: 325 mm(L)×225 mm(W)×145 mm(H)
Nhiệt độ hoạt động: -10℃~50℃
Độ ẩm tương đối: ≤90%,Không ngưng tụ
Chi tiết
General Information:
Turns ratio test is very important in order to find out the transformer has the right ratio corresponding on its rated voltage in primary and secondary. EPTTR-C is three phase, automatically test set specially designed for turns ratio, group test, PT and CT polarity measurements of power, distribution and instrument transformer.
Features:
- High speed and high accuracy because the total output is three-phase sine inverter, output voltage could adjust automatically, and soft start or soft stop function is equipped.
- Include three-phase transformer, single-phase transformer, PT, Z-type transformer turn ratio, group and polarity checking test function.
- Blind test function, which is testing transformers turns ratio or group without knowing high or low voltage connection methods.
- Angle differences test included in single-phase test.
- The maximum testable position of tap position is 197.
- The widest test range up to 10000.
- High and low voltage reverse connection protection function.
- Output short-circuit protection function.
- Clock and date display without power consumption; data storage methods consist of native storage and USB flash disk storage. Native storage could store 500 data which can be transfer and restore in USB flash disk; the data of USB flash disk is Word format, which can be edited and printed on the computer.
- The function of thermal printer, fast and noiseless.
- Small size and light weight.
-
-